Key Features
- PROFINET IO-Device interface module: IM 155-5 PN ST for SIMATIC ET 200MP electronics modules.
- Up to 30 IO modules: Supports up to 30 IO modules with additional PS in shared device mode.
- PROFINET connectivity: 1 PROFINET interface with 2 ports, RJ 45 (Ethernet), integrated switch, and 100BASE-TX.
- Diagnostics and synchronization: Supports isochronous mode, IRT, alarms, diagnostics function, and status indication LEDs.
- Engineering and update support: Configurable in STEP 7 TIA Portal from V15, with FW update possible and I&M0 to I&M3.
Applications
- ET 200MP PROFINET IO-Device integration: Connects an ET 200MP station as a PROFINET IO-Device.
- Shared device station operation: Supports shared device use with up to 2 IO Controllers.
- Networked I/O data exchange: Provides I/O data exchange over PROFINET with 2-port Ethernet connectivity.
- ISOchronous communication tasks: Supports isochronous operation with IRT and equidistant cycle timing.
Technical Summary
| Product type designation | IM 155-5 PN ST |
|---|---|
| Firmware version | V4.1.0 |
| FW update possible | Yes |
| Engineering with STEP 7 TIA Portal configurable/integrated from version | V15 |
| Supply voltage, rated value (DC) | 24 V |
| Supply voltage, permissible range, lower limit (DC) | 19.2 V |
| Supply voltage, permissible range, upper limit (DC) | 28.8 V |
| Input current, current consumption (rated value) | 0.2 A; at 24 V DC and without load |
| Input current, current consumption, max. | 1.2 A |
| Infeed power to the backplane bus | 14 W |
| Power consumption from the backplane bus | 2.3 W; in case of operation with separate system power supply to the left of IM |
| Address space per module, max. | 256 byte; For input and output data respectively |
| Address space per station, max. | 512 byte; For input and output data respectively |
| Number of PROFINET interfaces | 1; 2 ports (switch) |
| Interface types, RJ 45 (Ethernet) | Yes |
| Protocols, PROFINET IO Device | Yes |
Frequently Asked Questions
What is the Siemens 6ES7155-5AA01-0AB0?
It is an IM 155-5 PN ST PROFINET IO-Device interface module for SIMATIC ET 200MP.
How many IO modules does this IM 155-5 PN ST support?
It supports up to 12 IO modules without additional PS and up to 30 IO modules with additional PS in shared device mode.
What PROFINET interface details are available on this module?
It has 1 PROFINET interface with 2 ports, RJ 45 (Ethernet), an integrated switch, and 100BASE-TX transmission.
Which engineering software supports configuration of this module?
STEP 7 TIA Portal can configure and integrate it from version V15, and STEP 7 can use a GSD file.
What power supply range should be checked before ordering?