- Interface module type: IM 155-6 PN R1 for SIMATIC ET 200SP.
- PROFINET interface: 1 PROFINET interface with 2 ports (switch) and integrated switch.
- Station capacity: Supports max. 64 I/O modules and 256 submodules per station.
- Redundancy and service: R1 redundancy, multi hot swapping, and H-Sync forwarding.
- Electrical supply: Rated value (DC) 24 V, permissible range 19.2 V to 28.8 V, reverse polarity protection, and short-circuit protection.
- Diagnostics: RUN LED, ERROR LED, MAINT LED, ACT LED, PWR-LED, alarms, diagnostics function, and status indicator.
Applications
- PROFINET I/O station integration: Connection of a SIMATIC ET 200SP station as a PROFINET IO Device.
- Open IE communication: Communication over Open IE with TCP/IP, SNMP, and LLDP.
- PROFINET redundancy setup: Use in a PROFINET system with R1 redundancy and MRP client support.
Technical Summary
| Product type designation | IM 155-6 PN R1 |
|---|---|
| Firmware version | V6.1 |
| FW update possible | Yes |
| STEP 7 TIA Portal configurable/integrated from version | V19 |
| PROFINET from GSD version/GSD revision | GSDML V2.45 |
| Rated value (DC) | 24 V |
| Current consumption, max. | 700 mA |
| Power loss, typ. | 2.4 W |
| Quantity of operable ET 200SP modules, max. | 64 |
| Number of ports | 2; with BusAdapter |
| PROFINET IO Device | Yes |
| PROFINET system redundancy (R1) | Yes |
Frequently Asked Questions
What is the Siemens 6ES7155-6AU00-0HM0?
It is an IM 155-6 PN R1 interface module for SIMATIC ET 200SP.
How many ET 200SP modules does this interface module support?
The maximum quantity of operable ET 200SP modules is 64.
Which interfaces and ports are included on the module?
It has 1 PROFINET interface with 2 ports (switch), integrated switch, and RJ 45 (Ethernet) with BusAdapter.
What are the supply requirements for this module?
The rated supply voltage is 24 V DC, with a permissible range from 19.2 V to 28.8 V.
Which software or engineering version is supported for configuration?
STEP 7 TIA Portal is configurable/integrated from version V19, and PROFINET uses GSDML V2.45.