Key Features
- Central processing unit for S7-300: CPU 315F-2 PN/DP spare part with product type designation CPU 315F-2 PN/DP.
- Communication interfaces: 1st interface MPI/DP 12 Mbps, 2nd interface Ethernet PROFINET, with 2-port switch.
- Work memory and load memory: 512 KB work memory, plug-in Micro Memory Card required, with plug-in (MMC) load memory up to 8 Mbyte.
- Engineering software: Programming package: STEP 7 V5.5 or higher, Distributed Safety V5.4 SP4.
- Environmental and lifecycle details: Conformal coating, -25…+60 °C, product cancellation.
Applications
- PLC programming and engineering: Programming and engineering the CPU with STEP 7 V5.5 or higher and Distributed Safety V5.4 SP4.
- PROFIBUS DP and PROFINET communication: Connecting control communication through the MPI/DP interface and Ethernet PROFINET interface.
- Isochronous control: Using isochronous mode via PROFIBUS DP or PROFINET interface.
Technical Summary
| Product type designation | CPU 315F-2 PN/DP |
|---|---|
| Work memory | 512 kbyte |
| 1st interface | MPI/DP 12 Mbps |
| 2nd interface | Ethernet PROFINET |
| PROFINET switch | 2-port switch |
| Load memory | Plug-in (MMC) |
| Load memory, max. | 8 Mbyte |
| Supply voltage, rated value (DC) | 24 V |
| Supply voltage, permissible range | 20.4 V to 28.8 V |
| Power loss, typ. | 4.65 W |
| Current consumption, rated value | 750 mA |
| Current consumption, in no-load operation, typ. | 150 mA |
| Inrush current, typ. | 4 A |
| CPU processing time, bit operations, typ. | 0.05 μs |
| Programming package | STEP 7 V5.5 or higher, Distributed Safety V5.4 SP4 |
Frequently Asked Questions
What is Siemens 6AG1315-2FJ14-2AY0?
It is a SIPLUS S7-300 CPU 315F-2 PN/DP spare part based on 6ES7315-2FJ14-0AB0.
What communication interfaces does the CPU have?
It has a 1st interface MPI/DP 12 Mbps and a 2nd interface Ethernet PROFINET with a 2-port switch.
What power supply does this CPU require?
Rated value (DC): 24 V. Permissible range: 20.4 V to 28.8 V.
Which engineering software is specified for this CPU?
Programming package: STEP 7 V5.5 or higher, Distributed Safety V5.4 SP4.