Key Features
- 4 analog outputs: Analog output module with 4 channels in groups of 4.
- 16-bit resolution: Resolution with overrange: 16 bit.
- Diagnostics and substitute values: Diagnostics function: Yes. Substitute values connectable: Yes.
- 24 V DC supply: Rated value (DC): 24 V. Permissible range: 19.2 V to 28.8 V.
- Conformal coating: SIPLUS S7-1500 version with conformal coating.
- Engineering and firmware support: STEP 7 TIA Portal configurable/integrated from version see entry ID: 109746275. FW update possible: Yes.
Applications
- Analog signal output: Provides 4 analog voltage or current outputs for signal output tasks.
- Actuator connection: Supports connection of actuators with voltage output two-wire connection, voltage output four-wire connection, or current output two-wire connection.
Technical Summary
| Product type designation | AQ 4xU/I ST |
|---|---|
| Based on | 6ES7532-5HD00-0AB0 |
| Number of analog outputs | 4; > +60 °C max. 4x ±10 V permissible |
| Resolution with overrange (bit including sign), max. | 16 bit |
| Supply voltage, rated value (DC) | 24 V |
| Supply voltage, permissible range, lower limit (DC) | 19.2 V |
| Supply voltage, permissible range, upper limit (DC) | 28.8 V |
| Current consumption, max. | 190 mA; with 24 V DC supply |
| Power consumption from the backplane bus | 0.6 W |
| Power loss, typ. | 4 W |
| Cycle time (all channels), min. | 3.2 ms; independent of number of activated channels |
| Voltage output, short-circuit protection | Yes |
| Output ranges, voltage | 0 to 10 V |
| Output ranges, voltage 2 | -10 V to +10 V |
| Output ranges, current | 4 mA to 20 mA |
| Diagnostics function | Yes |
| Substitute values connectable | Yes |
| Run-time reparameterization | Yes |
| Run-time calibration | Yes |
| Isolation tested with | 750 V DC (type test) and according to EN 50155 (routine test) |
Frequently Asked Questions
What is the Siemens 6AG2532-5HD00-4AB0?
It is a SIPLUS S7-1500 AQ 4xU/I ST analog output module.
How many analog outputs does 6AG2532-5HD00-4AB0 provide?
It provides 4 analog outputs in groups of 4.
What supply voltage does this module require?
Rated supply voltage is 24 V DC, with a permissible range of 19.2 V to 28.8 V DC.
Which output ranges are supported?
Supported output ranges include 0 to 10 V, -10 V to +10 V, and 4 mA to 20 mA.
What selection details are available for installation and diagnostics?
The module supports diagnostics, substitute values, run-time reparameterization, run-time calibration, and a shielded cable length of up to 800 m.