Key Features
- Digital output module: DQ 8x230V AC/2A ST (triac) with 8 digital outputs.
- Output capacity: 8 channels in groups of 1; 2 A per group; 10 A per module max.
- Output voltage: Rated value (AC): 230 V; 120/230 V AC, 50/60 Hz.
- Diagnostics and signaling: RUN LED, ERROR LED, and channel status display with green LED.
- Installation and resilience: Conformal coating, -40…+70 °C, and substitute value support.
Applications
- 230 V AC digital load switching: Switching 230 V AC loads through 8 digital outputs.
- Redundant load control: Parallel switching of two outputs for redundant control of a load.
Technical Summary
| Product type designation | DQ 8×230 V AC/2A ST (triac) |
|---|---|
| Based on | 6ES7522-5FF00-0AB0 |
| Number of digital outputs | 8; > +60 °C number of simultaneously controllable outputs max. 8x 0.25 A, max. total current 2 A |
| Type of digital output | Triac |
| Rated output voltage | 230 V; 120/230 V AC, 50/60 Hz |
| Current per group, max. | 2 A; = Tmax; > +60 °C number of simultaneously controllable outputs max. 8x 0.25 A, max. total current per group 2 A |
| Current per module, max. | 10 A; = Tmax; > +60 °C number of simultaneously controllable outputs max. 8x 0.25 A, max. total current per group 2 A |
| Power consumption from the backplane bus | 0.9 W |
| Power loss, typ. | 10.8 W |
| Isolation tested with | 3 100 V DC |
Frequently Asked Questions
What is Siemens 6AG1522-5FF00-7AB0?
It is a SIPLUS S7-1500 digital output module, DQ 8x230V AC/2A ST (triac).
How many outputs does 6AG1522-5FF00-7AB0 provide?
It provides 8 digital outputs in groups of 1.
What output voltage and current does this module use?
Rated value (AC) is 230 V; 120/230 V AC, 50/60 Hz, with 2 A per group and 10 A per module max.
What diagnostics are available on 6AG1522-5FF00-7AB0?
It has a RUN LED, an ERROR LED, a channel status display, and substitute value support.
What should be checked before selecting this module?
Check the DQ 8×230 V AC/2A ST (triac) output type, 8-channel output count, 230 V AC rated value, and the selected cable length requirement of 1 000 m shielded or 600 m unshielded.