Key Features
- System power supply: Supplies the backplane bus of the S7-1500 with operating voltage.
- SIPLUS design: Based on 6ES7505-0RA00-0AB0 with conformal coating.
- Wide DC supply range: Rated value (DC): 24 V / 48 V / 60 V; permissible range lower limit (DC): 19.2 V; Static 19.2 V, dynamic 18.5 V; permissible range upper limit (DC): 72 V; Static 72 V, dynamic 75.5 V.
- Protection and isolation: Reverse polarity protection: Yes. Short-circuit protection: Yes. Primary/secondary electrical separation: Yes; Electrical isolation for 230 V AC (reinforced isolation).
Applications
- Backplane bus power supply: Supplies the backplane bus of the S7-1500 with operating voltage.
Technical Summary
| Product type designation | PS 60 W 24/48/60 V DC |
|---|---|
| Rated value (DC) | 24 V / 48 V / 60 V |
| Permissible range, lower limit (DC) | 19.2 V; Static 19.2 V, dynamic 18.5 V |
| Permissible range, upper limit (DC) | 72 V; Static 72 V, dynamic 75.5 V |
| Reverse polarity protection | Yes |
| Short-circuit protection | Yes |
| Infeed power to the backplane bus | 60 W; > +60 °C max. power input 30 W |
| IP degree of protection | IP20 |
| Ambient temperature during operation, min. | -40 °C; = Tmin (incl. condensation/frost); start-up @ -25 °C |
| Ambient temperature during operation, max. | 70 °C; = Tmax; > +60 °C max. power input 30 W; for vertical mounting position |
Frequently Asked Questions
What is the Siemens 6AG1505-0RA00-7AB0 product type?
It is a PS 60 W 24/48/60 V DC system power supply.
What DC supply values does 6AG1505-0RA00-7AB0 support?
Rated value (DC): 24 V / 48 V / 60 V. Permissible range lower limit (DC): 19.2 V; Static 19.2 V, dynamic 18.5 V. Permissible range upper limit (DC): 72 V; Static 72 V, dynamic 75.5 V.
What power output does the SIPLUS S7-1500 PS 1505 provide?
Infeed power to the backplane bus: 60 W; > +60 °C max. power input 30 W.
What are the installation and environmental limits for this power supply?
IP degree of protection: IP20. Ambient temperature during operation: -40 °C to 70 °C, with start-up at -25 °C.