Automation Spare Part

6AG1505-0KA00-7AB0

Send the exact MLFB, required quantity and delivery destination to request supply details for this Siemens automation spare part.

Product Specifications

Model / MLFB
6AG1505-0KA00-7AB0
Product Category
SIPLUS Power Supplies Systems
Product Code
6AG1505-0KA00-7AB0
Dimensions
15 × 15 × 4.3 cm
Weight
0.363 kg
Lifecycle
Announcement of product phase-out
Availability
in stock
Lead Time
Confirmed with quotation
Product Attachment
Download Datasheet
View products in this category

Product Description

Key Features

  • System power supply: Supplies the backplane bus of the S7-1500 with operating voltage.
  • SIPLUS S7-1500 PS 1505 25W 24VD: Product type designation: PS 25W 24VDC.
  • Conformal coating: Provided with conformal coating.
  • Wide operating temperature: Ambient temperature during operation: -40 °C to 70 °C; start-up @ -25 °C.
  • Product lifecycle: Announcement of product phase-out.

Applications

  • S7-1500 backplane bus supply: Supplies operating voltage to the S7-1500 backplane bus.
  • STEP 7 TIA Portal engineering: Engineering with STEP 7 TIA Portal configurable/integrated from version see entry ID: 109746275.

Technical Summary

Product type designation PS 25W 24VDC
Based on 6ES7505-0KA00-0AB0
Rated supply voltage 24 V; SELV
Permissible supply voltage, lower limit 19.2 V; Static 19.2 V, dynamic 18.5 V
Permissible supply voltage, upper limit 28.8 V; Static 28.8 V, dynamic 30.2 V
Reverse polarity protection Yes
Short-circuit protection Yes
Mains/voltage failure stored energy time 20 ms
Input current at 24 V DC 1.3 A
Infeed power to the backplane bus 25 W; > +60 °C max. power input 12.5 W
Power loss at nominal rating conditions 6.2 W
IP degree of protection IP20

Frequently Asked Questions

What is Siemens 6AG1505-0KA00-7AB0?

It is a SIPLUS S7-1500 PS 1505 25W 24VD system power supply.

What is the rated supply voltage for 6AG1505-0KA00-7AB0?

Rated supply voltage: 24 V; SELV.

What voltage range does 6AG1505-0KA00-7AB0 support?

Permissible supply voltage is 19.2 V to 28.8 V, with static and dynamic limits specified.

What protection and power data are specified for 6AG1505-0KA00-7AB0?

Reverse polarity protection and short-circuit protection are Yes, mains/voltage failure stored energy time is 20 ms, and infeed power to the backplane bus is 25 W.

Product Enquiry

Need Help With 6AG1505-0KA00-7AB0?

Email the model, required quantity and destination. For an installed or discontinued unit, include the hardware version and available nameplate details.