Key Features
- PROFINET interface module: IM 155-6 PN/2 HF with 1 PROFINET interface and 2 ports via BusAdapter.
- Module capacity: Max. 64 I/O modules, 16 ET 200AL modules, and 256 submodules per station.
- Redundancy and servicing: S2 redundancy, multi-hot swapping, and I&M data I&M0 to I&M3.
- Communication functions: PROFINET IO Device, Open IE communication, PROFINET MRP, IRT, PROFIenergy, prioritized startup, and shared device.
- Electrical data: Rated value (DC) 24 V, permissible range 19.2 V to 28.8 V, reverse polarity protection, and current consumption, max. 700 mA.
- Installation and diagnostics: 1 slot for BusAdapter, optional PN strain relief, RUN LED, ERROR LED, MAINT LED, PWR LED, and 2x green link LEDs on BusAdapter.
Applications
- PROFINET network integration: Connection of a PROFINET IO Device to a PROFINET network through the 2-port interface module.
- Open IE communication: Open IE communication over TCP/IP, SNMP, and LLDP.
- System redundancy operation: Use in PROFINET system redundancy with S2.
- Distributed I/O station expansion: Integration of up to 64 I/O modules and 16 ET 200AL modules in one station.
Technical Summary
| Product type designation | IM 155-6 PN/2 HF |
|---|---|
| Supply voltage, rated value (DC) | 24 V |
| Supply voltage, permissible range (DC) | 19.2 V to 28.8 V |
| Current consumption, max. | 700 mA |
| Power loss, typ. | 2.4 W |
| Modules per rack, max. | 64; + 16 ET 200AL modules |
| Number of submodules per station, max. | 256 |
| Number of PROFINET interfaces | 1; 2 ports (switch) |
| Number of ports | 2; via BusAdapter |
| BusAdapter (PROFINET) | Yes; Compatible BusAdapter: BA 2x RJ45, BA 2x FC, BA 2x SCRJ, BA SCRJ / RJ45, BA SCRJ / FC, BA 2x LC, BA LC / RJ45, BA LC / FC |
| PROFINET IO Device | Yes |
| Open IE communication | Yes |
| PROFINET system redundancy (S2) | Yes; NAP S2 |
| PROFINET MRP | Yes |
| Isochronous mode | Yes |
| Shortest clock pulse | 250 μs |
| Max. cycle | 4 ms |
| Jitter, max. | 1 μs |
| FW update possible | Yes |
| I&M data | Yes; I&M0 to I&M3 |
| Conformal coating | Yes |
| Isolation tested with | 750 V DC (type test) and according to EN 50155 (routine test) |
Frequently Asked Questions
What is Siemens 6AG2155-6AU01-4CN0 used for?
It is an IM 155-6 PN/2 HF SIPLUS ET 200SP interface module for PROFINET.
How many PROFINET ports does 6AG2155-6AU01-4CN0 have?
It has 2 ports via BusAdapter and 1 PROFINET interface with an integrated switch.
What is the power supply for 6AG2155-6AU01-4CN0?
Rated value (DC) is 24 V, with a permissible range of 19.2 V to 28.8 V.
How many I/O modules can be connected to 6AG2155-6AU01-4CN0?
The station supports up to 64 I/O modules and 16 ET 200AL modules.
What should be checked before selecting 6AG2155-6AU01-4CN0?
Check the required PROFINET interface setup, BusAdapter type, module capacity, and installation conditions such as supply voltage and mounting space.