Key Features
- Fail-safe analog input module: F-AI 4xI 0(4)..20mA 2-/4-wire HF with 4 analog inputs for current measurement.
- 2-wire and 4-wire transducer connection: Supports connection of signal encoders for current measurement as 2-wire transducer and as 4-wire transducer.
- Diagnostics and signaling: Diagnostics function, diagnostic alarm, monitoring of the supply voltage, wire break, short-circuit, and status LEDs for RUN, ERROR, PWR, and channels.
- Engineering support: STEP 7 TIA Portal configurable/integrated from version see entry ID: 109746275.
- Selection and installation details: Usable BaseUnits: BU type A0, A1; automatic encoding and electronic coding element type F are supported.
Applications
- Current measurement on 4 analog inputs: Measures current signals on 4 analog inputs.
- Connection of 2-wire transducers: Connects 2-wire transducers for current measurement.
- Connection of 4-wire transducers: Connects 4-wire transducers for current measurement.
- Engineering in STEP 7 TIA Portal: Configured and integrated in STEP 7 TIA Portal from version see entry ID: 109746275.
Technical Summary
| Product type designation | F-AI 4xI 0(4)..20mA 2-/4-wire HF |
|---|---|
| Number of analog inputs | 4 |
| Input ranges, current | 4 mA to 20 mA |
| Resolution with overrange | 16 bit |
| Supply voltage, rated value (DC) | 24 V |
| Supply voltage, permissible range | 19.2 V to 28.8 V |
| Current consumption, rated value | 0.38 A |
| Current consumption, max. | 0.4 A |
| Power consumption from the backplane bus | 70 mW |
| Power loss, typ. | 2 W |
| Isolation tested with | 750 V DC (type test) and according to EN 50155 (routine test) |
Frequently Asked Questions
What is the Siemens 6AG2136-6AA00-1CA1 product type?
It is a SIPLUS ET 200SP F-AI 4xI 2/4-wire HF analog input module.
How many analog inputs does this module have?
It has 4 analog inputs.
What current input ranges are supported by 6AG2136-6AA00-1CA1?
The module supports 0 to 20 mA and 4 mA to 20 mA input ranges.
What supply voltage does the module require?
Rated supply voltage is 24 V DC, with a permissible range of 19.2 V to 28.8 V.
Which installation and connection details are important for selection?
Usable BaseUnits are BU type A0 and A1, and the module is 15 mm wide, 73 mm high, and 58 mm deep.