Key Features
- Digital output module: DQ 4x24VDC/2A ST with 4 digital outputs and source output (PNP, current-sourcing).
- Selection and installation data: Suitable for BU type A0 and based on 6ES7132-6BD20-0BA0.
- Diagnostics and maintenance data: Diagnostics function, diagnostic alarm, monitoring of the supply voltage, wire break and short-circuit monitoring, and module diagnostics.
- Environmental version: Conformal coating with -40…+70 °C operation and OT4 with ST1/2 (+85 °C for 10 minutes).
- Electrical ratings: Supply voltage 24 V DC, permissible range 19.2 V to 28.8 V, and output voltage 24 V DC.
Applications
- Digital output control: Controls 4 digital outputs as source outputs for connected loads.
- Redundant load control: Supports parallel switching of two outputs for redundant control of a load.
- Digital input control: Controls a digital input.
Technical Summary
| Product type designation | DQ 4×24 V DC/2 A ST |
|---|---|
| Type of digital output | Source output (PNP, current-sourcing) |
| Number of digital outputs | 4 |
| Output voltage | 24 V |
| Supply voltage, rated value (DC) | 24 V |
| Supply voltage, permissible range, lower limit (DC) | 19.2 V |
| Supply voltage, permissible range, upper limit (DC) | 28.8 V |
| Current consumption, max. | 60 mA; without load |
| Power loss, typ. | 1 W |
| Address space per module, max. | 1 byte; + 1 byte for QI information |
| Potential separation between the channels and backplane bus | Yes |
| Isolation tested with | 750 V DC (type test) and according to EN 50155 (routine test) |
Frequently Asked Questions
What is Siemens 6AG2132-6BD20-4BA0?
It is a SIPLUS ET 200SP DQ 4×24 V DC/2 A ST digital output module.
How many digital outputs does 6AG2132-6BD20-4BA0 have?
It has 4 digital outputs.
What supply voltage does this module use?
The rated supply voltage is 24 V DC, with a permissible range of 19.2 V to 28.8 V DC.
What diagnostics are available on 6AG2132-6BD20-4BA0?
It includes diagnostics function, diagnostic alarm, monitoring of the supply voltage, wire break monitoring, short-circuit monitoring, and module diagnostics.
What installation or configuration details should be checked before selection?
Check that the module is suitable for BU type A0 and that the required engineering environment supports STEP 7 TIA Portal configurable/integrated from version see entry ID: 109746275.