Key Features
- BaseUnit type: BU type A1 with 1 slot.
- Terminal concept: Push-in terminal design with 16 process terminals, 2 terminals to P1 and P2 bus, and 0 AUX terminals.
- Operating range: Ambient temperature during operation: -40 °C to 70 °C for horizontal installation and -40 °C to 50 °C for vertical installation.
- Protection and coating: Conformal coating, with environmental product declaration, and isolation tested with 707 V DC (type test).
- Temperature acquisition: Hardware configuration includes a temperature sensor.
- Dimensions: Width: 15 mm, height: 117 mm, depth: 35 mm.
Applications
- ET 200SP module wiring: Provides push-in terminal connection for ET 200SP process terminals.
- P1 and P2 bus connection: Supports connection to the P1 and P2 bus with 2 terminals.
Technical Summary
| Product type designation | BU type A1 |
|---|---|
| based on | 6ES7193-6BP00-0DA1 |
| Rated value (DC) | 24 V |
| Current carrying capacity for P1 and P2 bus, max. | 10 A |
| Current carrying capacity for process terminals, max. | 2 A |
| Temperature sensor | Yes |
| Number of slots | 1; Type A1 |
| Terminal type | Push-in terminal |
| Conductor cross-section, min. | 0.14 mm2; AWG 26 |
| Conductor cross-section, max. | 2.5 mm2; AWG 14 |
Frequently Asked Questions
What is Siemens 6AG1193-6BP00-7DA1?
It is a SIPLUS ET 200SP BU15-P16+A0+2D/T BaseUnit, BU type A1, based on 6ES7193-6BP00-0DA1.
What terminals does 6AG1193-6BP00-7DA1 use?
It uses push-in terminals and provides 16 process terminals, 2 terminals to the P1 and P2 bus, and 0 AUX terminals.
What are the operating temperature limits of 6AG1193-6BP00-7DA1?
The ambient temperature during operation is -40 °C to 70 °C for horizontal installation and -40 °C to 50 °C for vertical installation.
What are the main selection dimensions for 6AG1193-6BP00-7DA1?
Width is 15 mm, height is 117 mm, and depth is 35 mm.
Does 6AG1193-6BP00-7DA1 include temperature sensing?
Yes. The hardware configuration includes a temperature sensor.