Key Features
- Analog input module: AI 4x U/I 2-wire with 4 analog inputs for voltage and current signal acquisition.
- Selection details: Suitable for BU type A0, A1 and color code CC03.
- Diagnostics and maintenance data: Module diagnostics, diagnostics function, I&M data I&M0 to I&M3, and FW update possible.
- Environmental design: Conformal coating and -40…+70 °C operating range.
- Measurement capability: 0 to +10 V, -10 V to +10 V, -5 V to +5 V, 0 to 20 mA, and 4 mA to 20 mA with 16 bit resolution.
Applications
- Analog signal acquisition: Acquires voltage and current input signals through 4 analog inputs.
- ET 200SP base unit integration: Connects to BU type A0 and A1 for 2-wire connection variants.
Technical Summary
| Product type designation | AI 4x U/I 2-wire |
|---|---|
| Based on | 6ES7134-6HD01-0BA1 |
| Number of analog inputs | 4; > 60 °C max. 1x ±20 mA or 4x ±10 V permissible |
| Supply voltage, rated value (DC) | 24 V |
| Supply voltage, permissible range | 19.2 V to 28.8 V |
| Current consumption, max. | 37 mA; without sensor supply |
| Encoder supply | 24 V; Yes |
| Encoder supply, output current, max. | 20 mA; max. 50 mA per channel for a duration < 10 s |
| Address space per module, max. | 8 byte; + 1 byte for QI information |
| Resolution with overrange, max. | 16 bit |
| Conversion time (per channel) | 180 / 60 / 50 ms |
| Basic error limit at 25 °C | Voltage, relative to input range, (+/-) 0.3 % |
Frequently Asked Questions
What is Siemens 6AG1134-6HD01-7BA1?
It is a SIPLUS ET 200SP AI 4xU/I 2-w analog input module.
How many analog inputs does 6AG1134-6HD01-7BA1 have?
It has 4 analog inputs.
What input ranges are supported by 6AG1134-6HD01-7BA1?
Supported ranges include 0 to +10 V, 1 V to 5 V, -10 V to +10 V, -5 V to +5 V, 0 to 20 mA, and 4 mA to 20 mA.
What supply voltage does the module require?
The rated supply voltage is 24 V DC, with a permissible range of 19.2 V to 28.8 V.
Which BaseUnits can be used with this module?
It is suitable for BU type A0 and A1.