Key Features
- 8 analog inputs: AI 8xI 2-/4-wire BA with 8 single-ended analog inputs for current measurement.
- 16 bit resolution: Provides 16 bit resolution, with up to 16 bit including sign for the -20 mA to +20 mA range.
- Module diagnostics: Includes diagnostics function, diagnostic alarm, supply voltage monitoring, and module diagnostics LED.
- SIPLUS conformal coating: Conformal coating with protection against fouling, Class 2 for high reliability.
- BaseUnit and installation fit: Suitable for BU type A0 and A1, with automatic encoding and Type A mechanical coding element.
Applications
- Current signal acquisition: Acquiring 0 to 20 mA, -20 mA to +20 mA, or 4 mA to 20 mA signals on 8 analog inputs.
- Connection of current transducers: Connecting current measurement as 2-wire transducer or 4-wire transducer.
- Analog input diagnostics: Monitoring supply voltage, wire break, short-circuit, group error, and overflow or underflow at the module.
Technical Summary
| Product type designation | AI 8xI 2-/4-wire BA |
|---|---|
| Based on | 6ES7134-6GF00-0AA1 |
| Number of analog inputs | 8; Single-ended |
| Supply voltage, rated value (DC) | 24 V |
| Supply voltage, permissible range, lower limit (DC) | 19.2 V |
| Supply voltage, permissible range, upper limit (DC) | 28.8 V |
| Current consumption (rated value) | 25 mA; rated voltage, all channels active, no load |
| Current consumption, max. | 725 mA; worst case voltage, all channels active, max. load, no derating |
| Input ranges | 0 to 20 mA; -20 mA to +20 mA; 4 mA to 20 mA |
| Resolution with overrange (bit including sign), max. | 16 bit |
Frequently Asked Questions
What is Siemens 6AG1134-6GF00-7AA1?
It is a SIPLUS ET 200SP AI 8xI 2-/4-wire BA analog input module.
How many analog inputs does 6AG1134-6GF00-7AA1 have?
It has 8 single-ended analog inputs.
What input current ranges are supported by this module?
The supported input ranges are 0 to 20 mA, -20 mA to +20 mA, and 4 mA to 20 mA.
What supply voltage does the module require?
The rated supply voltage is 24 V DC, with a permissible range from 19.2 V DC to 28.8 V DC.