Product Specifications

Model / MLFB
6AG1134-4GB11-2AB0
Product Category
SIPLUS ET 200 Systems
Product Code
6AG1134-4GB11-2AB0
Dimensions
9 × 6.2 × 2.3 cm
Weight
0.045 kg
Lifecycle
Product cancellation
Availability
in stock
Lead Time
Confirmed with quotation
Product Attachment
Download Datasheet
View products in this category

Product Description

Key Features

  • 2 analog inputs: Number of analog inputs: 2
  • Current measurement ranges: -20 mA to +20 mA; 4 mA to 20 mA
  • Diagnostics: Wire break, group error, and overflow/underflow
  • Signal smoothing: Parameterizable in four stages by means of digital filtering
  • Conformal coating and temperature range: Conformal coating, -25…+60 °C
  • Power and module load: Load voltage L+: 24 V; From power module

Applications

  • Current signal measurement: Measures current signals on 2 analog inputs for 2-wire transducers.

Technical Summary

Product function Isochronous mode: No
Number of analog inputs 2
Input ranges, currents -20 mA to +20 mA; Yes; 50 Ohm
Input ranges, currents 2 4 mA to 20 mA; Yes; 50 Ohm
Resolution with overrange 14 bit; ±20 mA: 14 bit, 4 to 20 mA: 13 bit
Conversion time per channel 65 ms; 55 / 65 ms
Load voltage L+ 24 V; From power module
Power loss, typ. 0.6 W
Address space per module, max. 4 byte
Isolation tested with 500 V DC
Diagnostics Wire break; Measuring range 4 to 20 mA only

Frequently Asked Questions

What is Siemens 6AG1134-4GB11-2AB0 used for?

It is a SIPLUS ET 200S EM 2AI I-4-wire transducer with 2 analog inputs for current measurement.

Which current input ranges does this module support?

It supports -20 mA to +20 mA and 4 mA to 20 mA.

What diagnostics are available on 6AG1134-4GB11-2AB0?

Wire break, group error, and overflow/underflow diagnostics are supported, with a group error SF (red) LED.

What power and wiring details are specified for selection?

Load voltage L+ is 24 V from the power module, and the shielded cable length is max. 200 m.