Product Specifications

Model / MLFB
6ES7405-0KR02-0AA0
Product Category
S7-400 PLC Systems
Product Code
6ES7405-0KR02-0AA0
Dimensions
29.5 × 23.3 × 6.3 cm
Weight
1.2 kg
Lifecycle
Active Product
Availability
in stock
Lead Time
Confirmed with quotation
Product Attachment
Download Datasheet
View products in this category

Product Description

Key Features

  • Power supply for SIMATIC S7-400: PS405 power supply for the SIMATIC S7-400 platform.
  • Wide-range DC input: Supports 24/48/60 V DC input.
  • Backplane bus output: Provides 5 V DC/10 A for the backplane bus.
  • Redundant use: Configured for redundant use.
  • Protection and isolation: Includes short-circuit protection, potential separation, and overvoltage category II.

Applications

  • SIMATIC S7-400 backplane bus power supply: Supplies 5 V DC power to the backplane bus.
  • Redundant power supply use: Supports redundant use in the SIMATIC S7-400 power supply setup.

Technical Summary

Product type SIMATIC S7-400 power supply PS405
Rated value (DC) 60 V DC
Output voltage type DC
Backplane bus output current (5 V DC), max. 10 A; no base load required
Backplane bus output current (24 V DC), max. 1 A; idling-proof
Input current at 24 V DC 4 A
Input current at 48 V DC 2 A
Input current at 60 V DC 1.6 A
Mains/voltage failure stored energy time 20 ms
Active power input, typ. 95 W
Power loss, typ. 20 W
Backup battery (optional) Yes; 2x lithium AA; 3.6 V / 2.2 Ah
Required slots 2
Potential separation Yes
Overvoltage category II
Equipment protection class I, with protective conductor

Frequently Asked Questions

What is the Siemens 6ES7405-0KR02-0AA0 used for?

It is a SIMATIC S7-400 PS405 power supply for the backplane bus.

What input voltages does this PS405 power supply support?

24/48/60 V DC.

What output current is available for the backplane bus?

The 5 V DC backplane bus output current is 10 A, with no base load required.

Does the 6ES7405-0KR02-0AA0 support redundant use?

Yes, it is specified for redundant use.

What installation and protection details should be checked before selection?

It requires 2 slots and includes short-circuit protection, potential separation, overvoltage category II, and equipment protection class I with protective conductor.