Key Features
- Fail-safe relay output module: SIMATIC DP electronics module for ET 200SP with 1 relay output (2 NO).
- Load switching capacity: Summation output current: 5 A. Load voltage: 24 V DC and 24.. 230 V AC.
- Diagnostics and status indication: Diagnostics function: Yes. RUN LED: Yes; green/red DIAG LED. Channel status display: Yes; green LED.
- Installation and coding: Usable BaseUnits: BU type F0. Automatic encoding: Yes. Mechanical coding element: Yes; type C.
- Engineering support: STEP 7 TIA Portal configurable/integrated from version V13. STEP 7 configurable/integrated from version V5.5 SP4 and higher.
Applications
- Relay switching of load circuits: Switches load circuits with 24 V DC and 24.. 230 V AC.
- Control of a digital input: Provides relay output control for a digital input.
Technical Summary
| Product type designation | F-RQ 24 … 48VDC/24 … 230VAC/5A ST |
|---|---|
| Usable BaseUnits | BU type F0 |
| Engineering with STEP 7 TIA Portal configurable/integrated from version | V13 |
| Engineering with STEP 7 configurable/integrated from version | V5.5 SP4 and higher |
| PROFINET from GSD version/GSD revision | V2.31 |
| Rated value (DC) | 24 V; Coil voltage |
| Permissible range, lower limit (DC) | 20.4 V |
| Permissible range, upper limit (DC) | 28.8 V |
| Power consumption from the backplane bus | 100 mW |
| Power loss, typ. | 1 W |
| Type of digital output | Relays |
| Number of digital outputs | 1 |
| Number of relay outputs | 1; 2 NO contacts |
| Rated supply voltage of relay coil L+ (DC) | 24 V |
| Current consumption of relays (coil current of all relays), max. | 70 mA |
Frequently Asked Questions
What is Siemens 6ES7136-6RA00-0BF0?
It is a SIMATIC DP electronics module for ET 200SP, F-RQ 1x 24 V DC/24..230VAC/5A ST.
How many relay outputs does this module have?
It has 1 relay output with 2 NO contacts.
What load voltage and output current does 6ES7136-6RA00-0BF0 support?
Load voltage is 24 V DC and 24.. 230 V AC, and the summation output current is 5 A.
What engineering software versions support this module?
STEP 7 TIA Portal supports it from version V13, and STEP 7 supports it from V5.5 SP4 and higher.
What should be checked before selecting this relay output module?
Check the required BaseUnit type F0, the 24 V DC coil supply range of 20.4 V to 28.8 V, and the load voltage and current limits.