Key Features
- Energy metering and line analysis: Supports energy measurement, power measurement, frequency measurement, active power measurement, reactive power measurement, power factor measurement, active factor measurement, reactive power compensation, and line analysis.
- Current transformer input: Designed for 1 A or 5 A current transformer connection; current measurement is supported and without current transformer is No.
- Diagnostics and alarms: Provides diagnostic alarm, limit value alarm, hardware interrupt, and diagnostics for line quality, supply voltage, parameter assignment error, module fault, channel not available, overflow/underflow, and overload current.
- ET 200SP selection details: Suitable for BU type U0, with automatic encoding, mechanical coding element type C, and any mounting position.
- Engineering and operating data: STEP 7 TIA Portal configurable/integrated from STEP 7 V16 or higher with HSP; STEP 7 configurable/integrated from V5.5 SP3 or higher; PROFINET from GSD version V2.3; PROFIBUS from one GSD file each, Revision 3 and 5 and higher.
Applications
- Energy and power monitoring: Measures voltage, current, energy, frequency, power, active power, reactive power, power factor, and active factor.
- Line quality analysis: Supports monitoring of instantaneous and half-wave values, THD measurement for current and voltage, harmonics for current and voltage, voltage dip (DIP), and voltage swell.
Technical Summary
| Product type designation | AI Energy Meter CT HF |
|---|---|
| Current transformer input | 1 A or 5 A current transformer |
| Supported power supply systems | TT, TN, IT |
| Supply voltage, rated value (DC) | 24 V |
| Supply voltage, permissible range, lower limit (DC) | 19.2 V |
| Supply voltage, permissible range, upper limit (DC) | 28.8 V |
| Cycle time (all channels), typ. | 50 ms; Time for consistent update of all measured and calculated values (cyclic und acyclic data) |
| Inputs | 256 byte |
| Outputs | 20 byte |
| Mounting position | any |
Frequently Asked Questions
What is the Siemens 6ES7134-6PA01-0CU0 used for?
It is a SIMATIC ET 200SP analog input module for energy measurement, power measurement, frequency measurement, and line analysis.
Which current transformer inputs does 6ES7134-6PA01-0CU0 support?
It supports 1 A or 5 A current transformer inputs.
What supply voltage does the module require?
Rated value (DC): 24 V. The permissible range is 19.2 V to 28.8 V.
Which engineering and communication details should be checked before selection?
STEP 7 TIA Portal configurable/integrated from STEP 7 V16 or higher with HSP, STEP 7 configurable/integrated from V5.5 SP3 or higher, PROFINET from GSD version V2.3, and PROFIBUS from one GSD file each, Revision 3 and 5 and higher.