Key Features
- Central processing unit for ET 200pro: SIMATIC DP, CPU 1513pro-2 PN for ET 200pro.
- Memory and processing: 600 KB for program and 2.5 MB for data, with 6 ns bit performance.
- PROFINET interfaces: 1st interface: PROFINET IRT with 3-port switch; 2nd interface: PROFINET RT.
- Protection and selection requirements: Degree of protection: IP65/67; SIMATIC Memory Card required; connection module required.
- Firmware and engineering: Firmware version V4.0; STEP 7 TIA Portal configurable/integrated from version V20 (FW V4.0) / V19 (FW V3.1) or higher.
Applications
- ET 200pro controller integration: Central processing for an ET 200pro-based controller setup.
- PROFINET network integration: Connection of PROFINET IRT and PROFINET RT networks through the two interfaces.
- Industrial communication and diagnostics access: Use of PROFINET, SIMATIC communication, Open IE communication, web server, and diagnostics functions.
Technical Summary
| Product type designation | CPU 1513pro-2 PN |
|---|---|
| Firmware version | V4.0 |
| Work memory for program | 600 kbyte |
| Work memory for data | 2.5 Mbyte |
| CPU processing times for bit operations, typ. | 6 ns |
| Supply voltage, rated value (DC) | 24 V |
| Supply voltage, permissible range, lower limit (DC) | 20.4 V |
| Supply voltage, permissible range, upper limit (DC) | 28.8 V |
| Degree of protection | IP65/67 |
| 1st interface | PROFINET IRT with 3-port switch |
| 2nd interface | PROFINET RT |
| Number of PROFINET interfaces | 2 |
| Number of ports | 3; 2x M12 + 1x RJ45 |
| SIMATIC Memory Card required | Yes |
Frequently Asked Questions
What is the Siemens 6ES7513-2PM03-0AB0?
It is a SIMATIC DP CPU 1513pro-2 PN for ET 200pro.
What communication interfaces does this CPU have?
It has 2 PROFINET interfaces: 1st interface: PROFINET IRT with 3-port switch and 2nd interface: PROFINET RT.
What memory and processing data define this model?
It provides 600 KB for program, 2.5 MB for data, and 6 ns bit performance.
What should be checked before selection or installation?
SIMATIC Memory Card required and connection module required; degree of protection: IP65/67; supply voltage rated value (DC): 24 V.