Key Features
- ET 200SP and ET 200AL station capacity: Supports max. 32 I/O modules and 16 ET 200AL modules.
- PROFINET interface with 2 ports: Provides 1 PROFINET interface with 2 ports (switch) and RJ 45 (Ethernet) via BusAdapter.
- Single hot swapping: Module swapping during operation is supported as single hot swapping.
- Diagnostics and status indication: Includes status indicator, alarms, diagnostics function, RUN LED, ERROR LED, MAINT LED, PWR-LED, and LINK TX/RX display.
- Firmware and engineering support: Firmware version V4.2 with FW update possible; configurable/integrated from STEP 7 TIA Portal version V14 and STEP 7 version V5.5 SP4.
- Supply and protection details: Rated value 24 V DC with permissible range 19.2 V to 28.8 V, reverse polarity protection, and short-circuit protection.
Applications
- PROFINET station integration: For connecting an ET 200SP station to a PROFINET network as a PROFINET IO Device.
- I/O module and station expansion: For operating ET 200SP I/O modules and ET 200AL modules within one station.
- Network operation with diagnostics and redundancy functions: For PROFINET communication with Open IE communication, MRP client support, and device diagnostics.
Technical Summary
| Product type designation | IM155-6PN ST, including BusAdapter BA 2xRJ45 |
|---|---|
| Firmware version | V4.2 |
| FW update possible | Yes |
| I&M data | Yes; I&M0 to I&M3 |
| Module swapping during operation (hot swapping) | Yes; Single hot swapping |
| Rated value (DC) | 24 V |
| Permissible range, lower limit (DC) | 19.2 V |
| Permissible range, upper limit (DC) | 28.8 V |
| Current consumption (rated value) | 450 mA |
| Power loss, typ. | 1.9 W |
| Quantity of operable ET 200SP modules, max. | 32 |
| Quantity of operable ET 200AL modules, max. | 16 |
Frequently Asked Questions
What is Siemens 6ES7155-6AA01-0BN0?
It is a SIMATIC ET 200SP PROFINET bundle IM, IM 155-6PN ST, including BusAdapter BA 2xRJ45.
How many modules can 6ES7155-6AA01-0BN0 operate?
It supports max. 32 ET 200SP modules and 16 ET 200AL modules.
Which communication interface does this model provide?
It provides 1 PROFINET interface with 2 ports (switch) and RJ 45 (Ethernet) via BusAdapter.
What power supply does 6ES7155-6AA01-0BN0 require?
The rated supply is 24 V DC, with a permissible range from 19.2 V to 28.8 V.
Can modules be swapped during operation?
Yes. It supports single hot swapping.