Key Features
- PROFIBUS DP device interface: IM 153-2 HF with Bus protocol/transmission protocol PROFIBUS DP to EN 50170.
- Up to 12 modules: Connection for ET 200M IM 153-2 High Feature for max. 12 S7-300 modules.
- Time stamp function: Time stamp support with 1 ms accuracy; 1 ms at up to 8 modules; 10 ms at up to 12 modules.
- RS 485 interface: Transmission procedure: RS 485, with transmission rate, max. 12 Mbit/s and automatic detection of transmission rate: Yes.
- Conformal-coated SIPLUS design: SIPLUS ET 200M variant with conformal coating and -40…+70 °C operating range; start up -25 °C.
Applications
- PROFIBUS DP remote I/O connection: Connection of ET 200M modules to a PROFIBUS DP device interface.
- Time-stamped digital input acquisition: Time stamping of digital input signals for event recording.
Technical Summary
| Product type designation | IM 153-2 HF |
|---|---|
| Based on | 6ES7153-2BA10-0XB0 |
| Firmware version | V6.0.0 |
| Rated value (DC) | 24 V |
| Supply voltage, lower limit (DC) | 20.4 V |
| Supply voltage, upper limit (DC) | 28.8 V |
| Number of modules per DP device interface, max. | 12 |
| Addressing volume, Inputs | 244 byte |
| Addressing volume, Outputs | 244 byte |
| Transmission rate, max. | 12 Mbit/s |
| Design of the connection | 9-pin sub D socket |
| IP degree of protection | IP20 |
Frequently Asked Questions
What is Siemens 6AG1153-2BA10-7XB0?
It is a SIPLUS ET 200M IM153-2 HF spare part based on 6ES7153-2BA10-0XB0.
How many S7-300 modules can this IM 153-2 HF connect?
It supports up to 12 S7-300 modules.
What power supply does 6AG1153-2BA10-7XB0 require?
Rated value is 24 V DC, with a permissible range from 20.4 V DC to 28.8 V DC.
Which interface and connector does the module use?
It uses RS 485, with a maximum transmission rate of 12 Mbit/s and a 9-pin sub D socket.