Key Features
- 4 digital outputs: Digital output module with 4 source outputs (PNP, current-sourcing).
- 24 V DC / 2 A output rating: Rated output voltage is 24 V DC, with 2 A per channel and 8 A per module.
- Diagnostics and status indication: Includes diagnostics function, diagnostic alarm, green PWR LED, green channel status LED, and green/red DIAG LED.
- BU type A0 and Type A coding: Suitable for BU type A0 and uses a mechanical coding element, Type A.
- Supply and protection data: Rated supply voltage is 24 V DC, with a permissible range of 19.2 V to 28.8 V and reverse polarity protection.
Applications
- Digital output switching: For switching 24 V DC loads through 4 source outputs.
- Redundant load control: Supports parallel switching of two outputs for redundant control of a load.
- Signal and load diagnostics: For monitoring supply voltage, wire break, short-circuit, and group error conditions.
Technical Summary
| Product type designation | DQ 4×24 V DC/2 A ST |
|---|---|
| Number of digital outputs | 4 |
| Type of digital output | Source output (PNP, current-sourcing) |
| Rated supply voltage | 24 V |
| Permissible supply voltage range | 19.2 V to 28.8 V |
| Output current for signal "1" rated value | 2 A |
| Current per module, max. | 8 A |
| Current per channel, max. | 2 A |
| Power loss, typ. | 1 W |
| Usable BaseUnits | BU type A0 |
| Engineering with STEP 7 TIA Portal from version | V11 SP2 / V13 |
| Engineering with PROFINET from GSD version/GSD revision | GSDML V2.3 |
Frequently Asked Questions
What is the Siemens 6ES7132-6BD20-0BA0?
It is a SIMATIC ET 200SP digital output module, DQ 4×24 V DC/2 A ST.
How many outputs does the 6ES7132-6BD20-0BA0 provide?
It provides 4 digital outputs.
What output rating does the 6ES7132-6BD20-0BA0 support?
The module is rated for 24 V DC outputs with 2 A per channel.
Which BaseUnit is suitable for the 6ES7132-6BD20-0BA0?
It is suitable for BU type A0.
What diagnostics are available on the 6ES7132-6BD20-0BA0?
It includes diagnostics function, diagnostic alarm, supply voltage monitoring, wire break, short-circuit, and group error information.