Key Features
- Serial interface module: SIPLUS ET 200S EM 1SI with one interface for RS 232, RS 422 and RS 485 signals.
- Integrated protocol drivers: Supports 3964 (R) and ASCII protocol drivers.
- 24 V DC supply: Rated value (DC): 24 V.
- Diagnostics indications: Diagnostics indication LED for Receive RxD, Transmit TxD and Group error SF (red).
- Conformal coating and temperature range: Conformal coating with -25…+70 °C operating temperature range.
Applications
- Serial communication with 3964 (R) protocol: Used for serial data exchange over RS 232 or RS 422/485 with the 3964 (R) protocol.
- Serial communication with ASCII protocol: Used for serial data exchange over RS 232 or RS 422/485 with the ASCII protocol.
- RS 232, RS 422 and RS 485 signal connection: Used to connect RS 232C, RS 422 and RS 485 signals through one interface.
Technical Summary
| Product type | SIPLUS ET 200S EM 1SI |
|---|---|
| Supply voltage, rated value (DC) | 24 V |
| Number of interfaces | 1 |
| Integrated protocol driver – 3964 (R) | Yes |
| Integrated protocol driver – ASCII | Yes |
| Transmission speed, RS 232 – with ASCII protocol, max. | 115.2 kbit/s; Full duplex: 110, 300, 600, 1 200, 2 400, 4 800, 9 600, 19 200, 38 400, 57 600, 76 800, 115 200 bps |
| Transmission rate, RS 422/485 – with 3964 (R) protocol, max. | 115.2 kbit/s; half duplex: 110, 300, 600, 1 200, 2 400, 4 800, 9 600, 19 200, 38 400, 57 600, 76 800, 115 200 bps |
| Signals – RS 232C | 8 (TxD, RxD, RTS, CTS, DTR, DSR, DCD, PE) |
| Power loss, typ. | 1.2 W |
| Ambient temperature during operation, min. | -25 °C; = Tmin |
Frequently Asked Questions
What is Siemens 6AG1138-4DF01-7AB0?
It is a SIPLUS ET 200S EM 1SI serial interface module.
Which interfaces and protocol drivers does this module provide?
It provides one interface with RS 232, RS 422 and RS 485 signals, and integrated 3964 (R) and ASCII protocol drivers.
What power supply does 6AG1138-4DF01-7AB0 use?
Rated value (DC): 24 V.
What connection limits should be checked for this module?
RS 232 cable length is 15 m max. and RS 485 cable length is 1 200 m max.