Key Features
- Fail-safe digital input module: SIMATIC DP electronic module for ET 200SP as F-DI 8x 24 V DC HF.
- 8 digital inputs: Digital inputs: 8, with parameterizable input behavior.
- Safety support: Up to PLe (ISO 13849-1) / SIL3 (IEC 61508).
- Diagnostics indication: RUN LED, ERROR LED, PWR LED, channel status display, and DIAG LED are supported.
- Engineering and communication data: Configurable in STEP 7 TIA Portal from SIMATIC Safety V20 and V21 or higher with HSP 0484, and PROFINET from GSDML V2.45.
- Mounting and base unit: 15 mm width and usable BaseUnits: BU type A0.
Applications
- Fail-safe digital input monitoring: Use for fail-safe acquisition of 24 V DC digital input signals on ET 200SP.
- Pulse counting and motion-related monitoring: Use the counter function for pulse counting, standstill monitoring, and speed monitoring.
Technical Summary
| Product type designation | F-DI 8x24VDC HF |
|---|---|
| Number of digital inputs | 8 |
| Rated value (DC) | 24 V |
| Safety rating | up to PLe (ISO 13849-1)/ SIL3 (IEC 61508) |
| Current consumption, max. | 40 mA; without load |
| Power loss, typ. | 2 W |
| Input voltage for signal "0" | -30 to +5 V |
| Input voltage for signal "1" | +15 to +30 V |
| Firmware version | V3.0 |
| FW update possible | Yes |
Frequently Asked Questions
What is Siemens 6ES7136-6BA01-0CA0 used for?
It is a SIMATIC DP electronic module for ET 200SP, F-DI 8x 24 V DC HF, for fail-safe digital input handling.
How many digital inputs does 6ES7136-6BA01-0CA0 have?
It has 8 digital inputs.
What supply voltage does the module use?
Rated value (DC): 24 V. The permissible range is 19.2 V to 28.8 V.
Which diagnostic and status indicators are available on this module?
RUN LED, ERROR LED, PWR-LED, channel status display, channel diagnostics LED, and DIAG LED are supported.
What engineering and PROFINET data are listed for selection?
STEP 7 TIA Portal configuration is supported from SIMATIC Safety V20 and V21 or higher with HSP 0484, and PROFINET uses GSDML V2.45.