Key Features
- DI 8x NAMUR HF: Digital input module with 8 NAMUR inputs.
- Conformal coating: Built for SIPLUS ET 200SP extreme conditions with conformal coating and -40…+70 °C operation, OT4 with ST1/2 (+85 °C for 10 minutes).
- Channel diagnostics: Supports diagnostic alarm, hardware interrupt, wire break monitoring, and short-circuit monitoring channel by channel.
- BU type A0: Suitable for BU type A0, with 2-wire connection and 3-wire connection support on BU type A0.
- PROFINET R1 IMs: Suitable for operation on PROFINET R1 IMs.
Applications
- 8-channel NAMUR digital input acquisition: Use for acquiring 8 NAMUR digital input signals.
- Channel-level diagnostics for input signals: Use for channel-by-channel diagnostic alarm, wire break, and short-circuit monitoring on the input channels.
Technical Summary
| Product type designation | DI 8xNAMUR HF |
|---|---|
| Based on | 6ES7131-6TF00-0CA0 |
| Number of digital inputs | 8; > +60 °C number of simultaneously controllable inputs max. 4 (no adjacent points) |
| Supply voltage, rated value (DC) | 24 V |
| Supply voltage, permissible range, lower limit (DC) | 19.2 V |
| Supply voltage, permissible range, upper limit (DC) | 28.8 V |
| Current consumption, max. | 70 mA |
| Power loss, typ. | 1.5 W |
| NAMUR encoder supply | 8.2 V |
| NAMUR encoder supply, output current per channel, max. | 8 mA |
| Address space per module, max. | 1 byte |
| Inputs | 42 byte; 1 byte + 1 byte for QI information in DI mode; 42 bytes in Counter mode |
| Outputs | 20 byte; 0 in DI mode; 20 bytes in Counter mode |
Frequently Asked Questions
What is Siemens 6AG2131-6TF00-4CA0?
It is a SIPLUS ET 200SP DI 8x NAMUR HF TX rail digital input module.
How many digital inputs does 6AG2131-6TF00-4CA0 provide?
It provides 8 digital inputs.
What supply voltage does this module use?
The rated supply voltage is 24 V DC, with a permissible range of 19.2 V to 28.8 V DC.
Which connection variant is supported for the BaseUnit?
It is suitable for BU type A0 and supports 2-wire connection and 3-wire connection on BU type A0.
What diagnostics are available on this input module?
It supports diagnostics function, diagnostic alarm channel by channel, hardware interrupt for channels 0 to 7, wire break monitoring, and short-circuit monitoring.