Key Features
- 16 digital inputs: Provides 16 digital inputs for DI operation.
- 24 V DC input module: Rated value (DC): 24 V with input voltage for signal "0" of -30 to +5 V and for signal "1" of +11 to +30V.
- Diagnostics and alarms: Diagnostics function: Yes. Diagnostic alarm: Yes. Diagnostic information readable: Yes. Monitoring the supply voltage: Yes.
- Installation and base unit fit: Suitable for BU type A0 and supports 1-wire connection with BU type A0, plus 2-wire, 3-wire, and 4-wire connection variants with BU type A0 + Potential distributor module.
- Environmental protection and temperature range: Conformal coating with operating range -40…+70 °C.
- Cable and delay data: Input delay is parameterizable from 0.05 / 0.1 / 0.4 / 0.8 / 1.6 / 3.2 / 12.8 / 20 ms, with shielded cable length up to 1 000 m and unshielded cable length up to 600 m.
Applications
- Digital input acquisition on an ET 200SP station: For reading 16 binary input signals in an ET 200SP setup.
Technical Summary
| Product type designation | DI 16x24VDC ST |
|---|---|
| Based on | 6ES7131-6BH01-0BA0 |
| Usable BaseUnits | BU type A0 |
| Color code for module-specific color-coded label | CC00 |
| I&M data | Yes; I&M0 to I&M3 |
| Rated supply voltage (DC) | 24 V |
| Permissible supply voltage range, lower limit (DC) | 19.2 V |
| Permissible supply voltage range, upper limit (DC) | 28.8 V |
| Current consumption, max. | 90 mA |
| Power loss, typ. | 1.7 W |
| Number of digital inputs | 16 |
| Input delay, parameterizable | 0.05 / 0.1 / 0.4 / 0.8 / 1.6 / 3.2 / 12.8 / 20 ms |
Frequently Asked Questions
What is Siemens 6AG1131-6BH01-7BA0 used for?
It is a SIPLUS ET 200SP DI 16×24 V DC digital input module.
How many digital inputs does 6AG1131-6BH01-7BA0 provide?
It provides 16 digital inputs.
What supply voltage does the module require?
Rated value (DC): 24 V; permissible range: 19.2 V to 28.8 V.
Which BaseUnit is suitable for this module?
It is suitable for BU type A0.
What diagnostics and input timing data are available?
It supports diagnostics for wire break and supply voltage, and the input delay is parameterizable from 0.05 / 0.1 / 0.4 / 0.8 / 1.6 / 3.2 / 12.8 / 20 ms.