Key Features
- 3 relay digital outputs: Type of digital output: Relays. Number of digital outputs: 3.
- Changeover contact outputs: Number of relay outputs: 3; Changeover contact, non-floating.
- Load switching capability: Rated switching voltage: 24 V DC to 120 V DC and 24V AC to 230V AC. Switching capacity of contacts: 5 A with resistive load and 2 A with inductive load.
- Diagnostics and substitute value output: Diagnostics function: Yes. Substitute values connectable: Yes. Diagnostic alarm: Yes. Monitoring the supply voltage: Yes.
- BaseUnit and configuration details: Suitable for BU type U0. STEP 7 TIA Portal configurable/integrated from version TIA V19 or higher with HSP0463 / integrated as of TIA V20.
- Electrical supply and protection: Supply voltage rated value: 24 V DC. Permissible range: 19.2 V to 28.8 V. Reverse polarity protection: Yes.
Applications
- Switching resistive loads: Switching resistive loads with relay outputs rated up to 5 A.
- Switching inductive loads: Switching inductive loads with relay outputs rated up to 2 A.
Technical Summary
| Product type designation | RQ 3x120VDC-230VAC/5A CO n.i. ST |
|---|---|
| Number of digital outputs | 3 |
| Number of relay outputs | 3; Changeover contact, non-floating |
| Rated switching voltage (DC) | 24 V DC to 120 V DC |
| Rated switching voltage (AC) | 24V AC to 230V AC |
| Switching capacity with resistive load | 5 A |
| Switching capacity with inductive load | 2 A |
| Supply voltage, rated value (DC) | 24 V |
| Supply voltage permissible range (DC) | 19.2 V to 28.8 V |
| Diagnostics function | Yes |
| Substitute values connectable | Yes |
| Suitable BaseUnit | BU type U0 |
Frequently Asked Questions
What is the Siemens 6ES7132-6HC70-0BU0 used for?
It is a SIMATIC ET 200SP relay module with 3 digital outputs.
How many relay outputs does 6ES7132-6HC70-0BU0 provide?
It provides 3 relay outputs with changeover contact and non-floating contacts.
What load and voltage ratings does this relay module support?
The contact rated switching voltage is 24 V DC to 120 V DC and 24V AC to 230V AC. Switching capacity is 5 A with resistive load and 2 A with inductive load.
What supply voltage does the module need?
The rated supply voltage is 24 V DC, with a permissible range of 19.2 V to 28.8 V.
Which BaseUnit and engineering version are supported?
The module is suitable for BU type U0 and is configurable in STEP 7 TIA Portal from TIA V19 or higher with HSP0463, or integrated as of TIA V20.