Key Features
- PROFINET interface module: IM 155-6 PN/2 HF for SIMATIC ET 200SP.
- 2-port interface with BusAdapter: 1 slot for BusAdapter and 2 ports with integrated switch.
- System capacity: Max. 64 I/O modules and 16 ET 200AL modules.
- High-availability and service functions: S2 redundancy, multi-hot swapping, isochronous mode, and included server module.
- Engineering and communication: STEP 7 TIA Portal configurable/integrated from version V15.1, PROFINET IO device, and Open IE communication.
Applications
- PROFINET network integration: Connects a SIMATIC ET 200SP station to PROFINET.
- Distributed I/O station expansion: Supports a station with up to 64 I/O modules and 16 ET 200AL modules.
- Open IE communication: Provides Open IE communication via TCP/IP, SNMP, and LLDP.
- Redundant station operation: Supports S2 redundancy and multi-hot swapping.
Technical Summary
| Product type designation | IM 155-6 PN/2 HF |
|---|---|
| Firmware version | V4.2 |
| FW update possible | Yes |
| STEP 7 TIA Portal configurable/integrated from version | V15.1 |
| Supply voltage, rated value (DC) | 24 V |
| Supply voltage, permissible range, lower limit (DC) | 19.2 V |
| Supply voltage, permissible range, upper limit (DC) | 28.8 V |
| Current consumption, max. | 700 mA |
| Power loss, typ. | 2.4 W |
| Address space per module, max. | 288 byte; For input and output data respectively |
| Quantity of operable ET 200SP modules, max. | 64 |
| Quantity of operable ET 200AL modules, max. | 16 |
| Transmission procedure | 100BASE-TX |
Frequently Asked Questions
What is the Siemens 6ES7155-6AU01-0CN0 product type?
It is an IM 155-6 PN/2 HF interface module for SIMATIC ET 200SP.
How many modules can this ET 200SP interface module handle?
It supports up to 64 I/O modules and 16 ET 200AL modules.
Which network and communication functions are included?
It provides PROFINET IO device, Open IE communication, TCP/IP, SNMP, and LLDP.
What are the supply voltage and current requirements?
Rated value is 24 V DC, with a permissible range from 19.2 V to 28.8 V DC and maximum current consumption of 700 mA.
Which engineering software version is supported?
STEP 7 TIA Portal configurable/integrated from version V15.1.